| 2ch Digital Indicating Controller |
| WCS-13A (48
x 48mm) |
・Features
・User defined combination
| |
Controller + Timer, Dual controller |
| |
Controller + Timer |
| |
 |
| |
Controller + Controller |
| |

|
・PV difference
input,Delay timer spec available
| |
PV difference input and delay timer spec are provided.
・PV difference input: Control is performed using the PV (CH1
PV-CH2 PV=PV).
・Delay timer: Timer output occurs using the DI (digital input). |
| |
PV difference input application
The heat source (heater) is controlled to maintain a constant
temperature difference between 2 points(A, B).
(e.g.) No condensation, defogging |
| |
 |
To the top of this
page
・Saves mounting
space
| |
As 2-unit function can be used with one unit,
mounting space can be reduced by half. |
| |

|
・Multiple CH2 functions
| |
CH2 function is selectable by front keypad as follows.
[If CH2 is of Multi-range input (-M), DC voltage input(-V)
or PV difference input (-S) spec]
・CH2 controller (2ch controller)
・CH1 output 2 (1-input 2-output)
・CH1 cooling output (Heating/Cooling control output)
・CH1 transmission output (effective when CH2 is DC current
output type)
・CH1 timer
|
| |
[If CH2 is based on delay timer (-T) spec]
・Delay timer 1 (independent timer output)
|
| |
・Delay timer 2 (Control and alarm action Start/Stop
interlocked with timer output)
|
| |
|
・Input/Output
type can be selected for CH1 and CH2.
| |
When ordering, Input/Output can be selected for
CH1 and CH2.
(If CH2 is based on delay timer (-T) spec, CH2 control output
is not available) |
| |
[Input]
・Multi-range input
Thermocouple, RTD, DC current, DC voltage (only 0-1V DC) can
be selected by keypad.
・DC voltage input
0-5V DC, 1-5V DC, 0-10V DC can be selected by keypad.
・Delay timer
・PV difference input
|
| |
[Control output]
・Relay contact: 1a
・Non-contact voltage (SSR drive): 12V DC 15%
・DC current: 4-20mA DC |
・Drip-proof/Dust-proof
| |
IP66 structure (for the front panel)
allows usage in harsh environments when the controller is exposed
to water or dust. |
To the top of this
page
・Specifications
・Rating
| Rated scale |
・Multi-range input
| Input |
Scale range |
| K |
-200 to 1370 |
-320 to 2500 |
| K |
-199.9 to 400.0 |
-199.9 to 750.0 |
| J |
-200 to 1000 |
-320 to 1800 |
| R |
0 to 1760 |
0 to 3200 |
| S |
0 to 1760 |
0 to 3200 |
| B |
0 to 1820 |
0 to 3300 |
| E |
-200 to 800 |
-320 to 1500 |
| T |
-199.9 to 400.0 |
-199.9 to 750.0 |
| N |
-200 to 1300 |
-320 to 2300 |
| PL-U |
0 to 1390 |
0 to 2500 |
| C(W/Re5-26) |
0 to 2315 |
0 to 4200 |
| Pt100 |
-199.9 to 850.0 |
-199.9 to 999.9 |
-200 to 850 |
-300 to 1500 |
| JPt100 |
-199.9 to 500.0 |
-199.9 to 900.0 |
-200 to 500 |
-300 to 900 |
| 4-20mA(*1) |
-1999 to 9999(*2) |
| 0-20mA(*1) |
| 0-1V |
(*1): For DC current input, 50
shunt resistor (sold separately) should be connected
(*2): For DC current and voltage input, scaling and decimal
point place selection are required.
・DC voltage input
|
Input
|
Scale range
|
|
0-5V
|
-1999 to 9999(*)
|
|
1-5V
|
|
0-10V
|
(*): For DC voltage input, scaling and decimal point place selection
are required.
|
| Input |
TC |
K, J, R, S, B, E, T, N, PL-U, C(W/Re5-26)
External resistance: 100
or less
However, B input; External resistance 40
or less |
| RTD |
Pt100, JPt100 3-wire system
Allowable input lead wire resistance: Resistance 10
or less per wire |
| DC current |
0-20mA DC, 4-20mA DC
Input impedance; 50
(50
shunt resistor should be connected between input terminals)
Allowable input current; 50mA DC or less (when 50
shunt resistor is used) |
|
DC Voltage
|
0-1V DC
Input impedance: 1M
or more, Allowable input voltage: 5V DC or less
Allowable signal source resistance: 2k
or less |
0-5V DC, 1-5V DC, 0-10V DC
Input impedance: 100k
or more, Allowable input voltage: 15V DC or less
Allowable signal source resistance: 100
or less |
| Supply voltage |
100 to 240V AC 50/60Hz
24V AC/DC 50/60Hz |
| Allowable fluctuation
range |
85 to 264V AC
20 to 28V AC/DC |
・General structure
| Dimensions |
48x48x106.5mm (WxHxD) |
| Mounting |
Flush (Mountable panel thickness: 1 to 8mm) |
| Display |
CH1(CH2) PV/SV display: 8x40mm (HxW) |
・Indication accuracy
・Control performance
・Standard functions
| Alarm
output |
Alarm type can be selected by keypad
・High limit alarm
・Low limit alarm
・High/Low limits alarm
・High/Low limit range alarm
・Process high alarm
・Process low alarm
・High limit alarm with standby
・Low limit alarm with standby
・High/Low limits alarm with standby
Setting accuracy: The same as the indication accuracy
Action: ON/OFF action
Hysteresis: Thermocouple, RTD input: 0.1 to 100.0 ( )
DC current, voltage input: 1 to 1000
Output: Relay contact 1a, Control capacity: 3A 250V AC (resistive
load), Electric life: 100,000 cycles
|
|
Heating/Cooling control output
|
If CH1 cooling output is selected during CH2 function selection,
the unit will be of 1ch Heating/Cooling control output specification.
So CH1 will match OUT1 (Heating output), and CH2 will match
OUT2 (Cooling output ) of CH1.
OUT2 proportional band: 0.0 to 10.0 times OUT1(CH1) proportional
band (ON/OFF action when set to 0.0)
OUT2 integral time,OUT2 derivative time: The same as those
of OUT1(CH1) integral and derivative time
OUT2 proportional cycle: 1 to 120sec
Overlap/Dead band: Thermocouple, RTD input: -100.0 to 100.0 ( )
DC current, voltage input: -1000 to 1000 (The placement of
the decimal point place follows the selection)
OUT2 ON/OFF hysteresis: Thermocouple, RTD input: 0.1 to 100.0 ( )
DC current, voltage input: 1 to 1000 (The placement of the
decimal point place follows the selection)
OUT2 high limit: 0 to 100% (DC current output type: -5 to
105%)
OUT2 low limit: 0 to 100% (DC current output type: -5 to 105%)
OUT2 action mode: Air cooling (linear characteristic), Oil
cooling (1.5th power of the linear characteristic), Water
cooling (2nd power of the linear characteristic)
Selectable by front keypad
Control output: Refer to the "Control output" section.
|
| Delay timer |
Between DI terminals Open: OFF
Between DI terminals Closed: ON
Circuit current when closed: 6mA |
| Transmission
output |
If CH1 transmission output (Effective when CH2 is DC current
output type) is selected
during CH2 function selection: Converting the value (PV, SV
or MV transmission) to analog signal every 0.5 seconds, outputs
the value in current.
Resolution: 1/8192
Current: 4-20mA DC
Load resistance: Max. 550
Output accuracy: Within 0.3%
of the transmission output scaling span
|
| Attached functions |
Sensor correction, Set value lock, Power failure
countermeasure, Self-diagnosis, Automatic cold junction temperature
compensation, Burnout, Input abnormality, Warm-up indication,
CH2 function selection |
・Options
|
Color Black[BK]
|
Panel frame, Case: Black |
| Terminal cover [TC] |
Electric shock protection terminal cover
Be sure to use this terminal cover option if the operator may
be in contact with the back of the controller while it is running. |
・Insulation, Dielectric strength
|
Insulation resistance
|
10M
or more, at 500V DC |
|
Dielectric strength
|
Between Input terminal - Power terminal: 1.5kV
AC for 1 minute
Between Output terminal - Power terminal: 1.5kV AC for 1 minute |
・Other
| Ambient temperature |
0 to 50 |
| Ambient humidity |
35 to 85%RH (Non-condensing) |
| Drip-proof/ Dust-proof |
IP66 for the front panel |
To the top of this page
・Terminal arrangement
Terminal arrangement
| If CH2 is of Multi-range input (-M),
DC voltage input(-V) or PV difference input (-S) spec |
| |
 |
| |
|
| If CH2 is based on delay timer (-T) spec |
| |
 |
・External
dimensions
External dimensions (Scale: mm)
Panel cutout (Scale: mm)
To the top of this
page
|