| [Between SIF-200-GCS and PLC unit] |
Communication line
|
: |
RS-232C/RS-422A |
[Between SIF-200-GCS and GCS-300] |
Communication line
|
: |
RS-485 |
| Communication method |
: |
Half-duplex communication start-stop synchronization |
| Communication speed |
: |
9600/19200bps (Selectable by DIP switch) |
| Data format |
: |
Start bit (1), Data bit (7 or 8) Selectable
by DIP switch
Parity (even, odd or no parity) Selectable by DIP switch
Stop bit (1 or 2) Selectable by DIP switch |
PLCs corresponding
to SIF-200-GCS |
: |
PLCs are selectable by rotary switch.
Omron Corp.  C200H*
Mitsubishi Electric Corp.  A2N*
Mitsubishi Electric Corp.
FX2N*
Fuji Electric Co., Ltd. MICREX-F70* |
| Supply voltage |
: |
100 to 240V AC 50/60Hz |
| Power consumption |
: |
Approx. 5VA |
| Insulation resistance |
: |
Between [Power terminal and
Ground terminal], [Ground terminal
and Digital output], [Power terminal and Digital input], [Digital
output and Ground terminal], [Digital input and Ground terminal]
10M
or more, at 500V DC |
| Case |
: |
Flame-resistant resin, Black |
| Mounting |
: |
DIN rail mounting |
| Dimensions |
: |
48(W) x 96(H) x 100(D)mm (including round
type socket) |
| Weight |
: |
Approx. 320g |
|
|
|
| * Product names written above are registered