Shinko Technos for temperature and humidity control
Japanese
SHINKO TECHNOS CO., LTD.
Contact
HOME Company Profile Quality&Environmental Activities Products Support&Downloads Applications
Programmable Controller
PCA1 NEW
 

-Program capacity with 16-patterns, 16-steps
-Easily legible LCD display with 11-segment characters
-Efficient Monitoring software
-Enhanced serial communication function
-Drip-proof/Dust-proof (IP66)
-Dimensions
-Specifications

PCA1_photo

Program capacity with 16-patterns, 16-steps
Program capacity: 16-patterns, 16-steps
Program control of up to 256 steps is possible by linking patterns.
PCA1_pattern

TOP
Easily legible LCD display with 11-segment characters
11-segment character LCD display is used, so characters can be read easily.
PCA1_11-segment


Industry-leading premium display
PV Display: 24.0 x 11.0 mm (H x W)
SV/MV/TIME Display: 14.0 x 7.0 mm (H x W)


PCA1 and PC-900 comparison

PCA1PC-900
PCA1_�\���� PC-900_�\����


PV color changes linked with alarm
PV color changes: Orange, Green, Red, When any alarm is ON: Green -->
Red, When any alarm is ON: Orange --> Red, or PV color changes by deviation between PV and SV.
Errors can be also checked via action indicators.
PCA1_PV_color


Backlight indication time
By setting backlight time (from no operation status until backlight is switched off), displays can be turned off, resulting in energy savings.

TOP

Efficient Monitoring software
Monitoring software (SWM-PCA01M) is available for data monitoring, editing, loading, etc.
Power to the PCA1 is not required if USB communication cable (CMB-001) is used.
PC_PCA1_�ڑ�
TOP

Enhanced serial communication function
Communication protocol: Shinko protocol, Modbus ASCII , and Modbus RTU
Modbus ASCII, Modbus RTU: A maximum of 100 pieces of multiple data Read/Write is possible.

TOP

Drip-proof/Dust-proof structure
IP66 (for front panel only), usable in harsh environments where dust is present or water splashes.

TOP

Dimensions
PCA1_dimension
TOP

Specifications
Input
Input
Thermocouple K, J, R, S, B, E, T, N, PL-II, C(W/Re5-26)
External resistance: 100 max.
However, B input: External resistance: 40 max.
RTD Pt100, JPt100 3-wire type
Allowable input lead wire resistance: 10 max. per wire
However, Pt100, -100.0 to 100.0 : 5 max. per wire
Direct current 0 - 20 mA DC, 4 - 20 mA DC
Input impedance: 50
Allowable input current: 100 mA max.
DC voltage 0 - 10 mV DC, -10 - 10 mV DC, 0 - 50 mV DC,
0 - 100 mV DC, 0 - 1 V DC:
Input impedance: 1 M min.
Allowable input voltage: 5 V DC max.
Allowable signal source resistance: 2 k max. (0 - 1 V DC)
200 max. (0 - 100 mV DC, 0 - 50 mV DC)
40 max. (-10 - 10 mV DC)
20 max. (0 - 10 mV DC)
0 - 5 V DC, 1 - 5 V DC, 0 - 10 V DC
Input impedance: 100 k min.
Allowable input voltage: 15 V DC max.
Allowable signal source resistance: 100 max.


Output
Control output
Relay contact
1a1b
Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (Inductive load cos=0.4)
Electrical life: 100,000 cycles
Non-contact voltage
(For SSR drive)
12 V DC15%
Max 40 mA (Short circuit protected)
Direct current

4 to 20 mA DC
Resolution: 12000
Load resistance: Max 600


Event output
EV1 - EV4
Relay contact
1a
Control capacity: 3 A 250 V AC (resistive load)
1 A 250 V AC (inductive load cos=0.4)
Electrical life: 100,000 cycles
Event output EV3, EV4 share one common terminal.


Performance
Reference accuracy
Thermocouple

Within 0.2% of each input span1 digit
However, R, S input 0 to 200 (32 to 392): Within 6 (12)
B input, 0 to 300 (0 to 572): Accuracy is not guaranteed.
K, J, E, T, N input, Less than 0 (32): Within 0.4% of input span1 digit

RTD Within 0.1% of each input span1 digit
Direct current,
DC voltage
Within 0.2% of each input span1 digit

Cold junction compensation accuracy

Within 1, at 0 to 50
Input sampling period 125 ms
Time indication accuracy 0.1% of setting time
Setting accuracy Based on Reference accuracy and Cold junction compensation accuracy
Time setting accuracy 0.1% of setting time
Setting resolution
Temperature Thermocouple, RTD input without decimal point:
1 ()
Thermocouple, RTD input with decimal point:
0.1 ()
DC voltage, current input: 1
Time 1 minute or 1 second

Program Performance
Number of patterns 16 (Linkable)
Number of steps 256 (16 steps/pattern)
Repetitions 0 to 9999 times (Repetitions disabled when set to 0.)
Program time range 0 to 99 hours 59 minutes/step, or 0 to 99 minutes 59 seconds/step
(When ----- is set, Fixed value control is performed using step SV.)
Wait value Thermocouple, RTD input without decimal point:
(0 to 100) ()
Thermocouple, RTD input with decimal point:
(0.0 to 100.0) ()
DC voltage, current input:
(0 to 1000) (The placement of the decimal point follows the selection.)
(The Wait action is disabled when set to 0 or 0.0.)



Products
Temperature & Programmable Controllers
Signal
Conditioners
System Products,
Comm. Converters
Indicators
Recorders,
Data Loggers

Portable, Other
Input Devices
Output Devices


TOP

Downloads Catalogs Contact

HOME | Company Profile | Quality & Environmental Activities | Products
Support & Downloads | Applications | Discontinued Products
CE conformity & UL Approved Products | RoHS Directive | Privacy Policy | Terms of Use
Japanese | Sitemap