Usage selection |
|
|
|
|
|
 |
|
|
|
|
|
|
|
|
|
|
|
| 2-POINT POWER CONTROL UNIT |
| APR-102 |
|
E2
individual displays/outputs,
2 output ON/OFF keys built-in
2-point individual displays/outputs,
2 output ON/OFF keys usable with ease |
| @ |
@ |
@ |
|
Traditional power control unit
|
|
APR-102
|
|
|
|
|
| @ |
@ |
@ |
| Merits of the APR-102 |
| @ |
2 individual display makes electric
energy calculation convenient |
| @ |
High accuracy signal output |
| @ |
2 individual output ON/OFF key for CH1/CH2 |
EWide
range of usage as a power control unit
| The APR-102 can be used for the following
usage. |
| @ |
Air fan |
| @ |
Motor rotation control |
| @ |
Incandescent dimming |
| @ |
Heater power control |
To
the top of this page
ESpecifications
ERating
| Input voltage |
190 to 250V AC 50/60Hz (unit and load power
input) |
| Output voltage |
Voltage corresponding to phase angle 0 to
166 degrees |
| Output current |
0.2 to 2A AC (Max. 3A AC) |
| Voltage indication |
Voltage corresponding to phase angle 0 to
166 degrees (Indication error: Within 10%
of input voltage) |
EGeneral structure
| Case material |
Flame-resistant resin |
| Case color |
Black |
| Panel |
Membrane sheet |
| Dust-proof/Drip-proof |
IP66 for front face |
| Display |
Output voltage display (CH1, CH2): 7-segment,
red, 3-digit numeric value indication
Character size: 8x4mm (HxW) |
EInstallation specifications
| Dimensions |
48x96x110mm (WxHxD) |
| Mounting |
Flush |
| Weight |
Approx. 250g |
| Power consumption |
Approx. 12VA (Inner power consumption when
each load is 2A AC) |
| Ambient temperature |
0 to 55 |
| Ambient humidity |
35 to 85%RH (Non-condensing) |
| Accessories |
Instruction manual: 1copy, Mounting brackets:
1set |
ESetting structure
| Output voltage
setting |
Sets the output voltage using
the UP/DOWN key, while viewing voltage indicated on the
Output voltage display. |
| Setting range |
Voltage corresponding to phase angle 0 to
166 degrees |
| Output ON/OFF |
By pressing the output ON/OFF key, output
is turned ON or OFF for CH1 or CH2.
For output ON, output voltage is indicated on the CH1/CH2
output voltage display.
For output OFF, [
] is indicated on the CH1/CH2 output voltage display. |
|
Load burnout indication
|
If load (heater) is burnt out, and if output
is turned on,
[
] flashes on the CH1/CH2 output voltage display. |
EInsulation, dielectric strength
| Insulation
resistance |
10M
ormore, at 500V DC |
| Dielectric
strength |
Power terminal - Ground terminal: 1.5kV
AC for 1min
Output terminal- Ground terminal: 1.5kV AC for 1min |
To
the top of this page
External dimensions (Scale: mm)
| @ |
 |
| @ |
@ |
Panel cutout (Scale:
mm)
| @ |
 |
| @ |
@ |
Name and functions
| @ |
 |
| @ |
(1) |
CH1 output voltage display |
Indicates CH1 output voltage. |
| @ |
(2) |
CH1 output ON/OFF key |
Turns CH1 output ON or OFF. |
| @ |
(3) |
CH1 output voltage DOWN key |
Decreases CH1 output voltage. |
| @ |
(4) |
CH1 output voltage UP key |
Increases CH1 output voltage. |
| @ |
(5) |
CH2 output voltage display |
Indicates CH2 output voltage. |
| @ |
(6) |
CH2 output ON/OFF key |
Turns CH2 output ON or OFF. |
| @ |
(7) |
CH2 output voltage DOWN key |
Decreases CH2 output voltage. |
| @ |
(8) |
CH2 output voltage UP key |
Increases CH2 output voltage. |
Terminal arrangement
| @ |
 |
| @ |
AC INPUT |
Power supply |
| @ |
LOAD1 |
Load 1 |
| @ |
LOAD2 |
Load 2 |
| @ |
GND |
Ground |
|
To the top of this
page
|
|